High Power Laser and Particle Beams, Volume. 37, Issue 7, 075003(2025)

Field-line coupling characteristics of relay protection device under strong electromagnetic pulse

Dingding Yao1, Weidong Zhang1, Long Jin2, Zexin Zhou2, and Guanglong Zhou1
Author Affiliations
  • 1State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources, North China Electric Power University, Beijing 102206, China
  • 2National Key Laboratory of Power Grid Safety, China Electric Power Research Institute, Beijing 100192, China
  • show less
    Figures & Tables(15)
    Test equipment layout and relay protection device
    High-altitude electromagnetic pulse and its field-line coupling mode
    Electromagnetic pulse test environment and equipment layout
    Measurement system
    Measured electric field and electric field under empty space
    Common mode current on the cable
    Operation interface of relay protection device
    Simulation and comparison of near field-line coupling
    Pulse current injection test layout
    Schematic diagram of the action of strong electromagnetic pulse
    Far field-line coupling model
    • Table 1. Abnormal condition of relay protection device

      View table
      View in Article

      Table 1. Abnormal condition of relay protection device

      output voltage of electrical fast transient/Vtest phenomenon
      500no phenomenon
      800no phenomenon
      1000the main screen goes back to“protection start”
      1500do not attempt single-phase trip, directly perform three-phase trip
      2000directly perform three-phase trip and send “accelerated intertrip” order
    • Table 2. High altitude electromagnetic pulse test results

      View table
      View in Article

      Table 2. High altitude electromagnetic pulse test results

      field intensity/(kV/m)common mode current on signal line/Atest phenomenon
      4.506.99——
      6.4110.09——
      9.0613.62——
      14.4322.57——
      19.5129.91——
      21.6831.18——
      23.1732.45maloperation/extended operation time
      24.2533.98maloperation
      25.6936.10maloperation
      25.5836.95maloperation
      29.8342.45maloperation
      31.2341.73maloperation
      34.4045.12maloperation
    • Table 3. pulse current injection test results

      View table
      View in Article

      Table 3. pulse current injection test results

      pulse injection source voltage/kVcommon mode current on signal line/Atest phenomenon
      1619.52——
      1822.40——
      2025.28——
      2230.10——
      2434.90——
      2636.70——
      2836.92maloperation
      3042.68maloperation
      3247.16maloperation
    • Table 4. Field line coupling simulation results

      View table
      View in Article

      Table 4. Field line coupling simulation results

      cable typeshielding current peak value/Acore current peak value/A
      secondary cable grounded on both sides of shield layer and armor layer37.110.17
      secondary cable grounded on both sides of shield layer50.150.19
      secondary cable grounded on one side of the shield layer50.1611.55
      ungrounded secondary cable——11.55
      signal cable in cabinet——0.08
    Tools

    Get Citation

    Copy Citation Text

    Dingding Yao, Weidong Zhang, Long Jin, Zexin Zhou, Guanglong Zhou. Field-line coupling characteristics of relay protection device under strong electromagnetic pulse[J]. High Power Laser and Particle Beams, 2025, 37(7): 075003

    Download Citation

    EndNote(RIS)BibTexPlain Text
    Save article for my favorites
    Paper Information

    Category:

    Received: Jan. 15, 2025

    Accepted: Jun. 3, 2025

    Published Online: Jul. 18, 2025

    The Author Email:

    DOI:10.11884/HPLPB202537.250014

    Topics