Chinese Journal of Ship Research, Volume. 18, Issue 5, 234(2023)

Study on supercritical carbon dioxide Brayton cycle cooling source disturbance control

Yuwei SUN1,2, Fulin LIU1,2, Wei WEI3, Chengqing YUAN2,3, and Zhenguo SONG4
Author Affiliations
  • 1School of Naval Architecture , Ocean and Energy Power Engineering, Wuhan University of Technology, Wuhan 430063, China
  • 2National Engineering Research Center for Water Transport Safety, Wuhan University of Technology, Wuhan 430063, China
  • 3School of Transportation and Logistics Engineering, Wuhan University of Technology, Wuhan 430063, China
  • 4China Ship Development and Design Center, Wuhan 430064, China
  • show less

    Objectives

    This paper aims to cope with the possible impact of external condition disturbances on the operating parameters of a supercritical carbon dioxide (S-CO2) Brayton cycle power generation system and ensure its efficient, safe and stable operation.

    Methods

    A dynamic numerical simulation model of a simple S-CO2 Brayton cycle power generation system is built using the Matlab/Simulink platform, and the transient operation characteristics of the system are analyzed. The change laws of the operating parameters of the thermodynamic cycle system under changing cooler parameters are then simulated, and the influence of the temperature fluctuation of the cooling source on the inlet and outlet parameters of the system components, system cycle efficiency and adjustment methods are analyzed.

    Results

    The results show that the maximum error between the established system transient simulation model results and the experimental results is 3.658%; a 2 K increase in the cooling water temperature will lead to a 1.4 K increase in the compressor inlet temperature, and the system will need 300 s to restore stability; after adding a PID control system, the compressor inlet temperature change amplitude is reduced by 50% and the system stabilization time is reduced by 62%.

    Conclusions

    The established model can accurately reflect the operation of the system. Based on the opposition of the influence of cooling water temperature increase and flow increase on the system, the proposed PID control system can ensure that the carbon dioxide working fluid in the system is always above the critical point, thereby ensuring the safe and stable operation of the system.

    Tools

    Get Citation

    Copy Citation Text

    Yuwei SUN, Fulin LIU, Wei WEI, Chengqing YUAN, Zhenguo SONG. Study on supercritical carbon dioxide Brayton cycle cooling source disturbance control[J]. Chinese Journal of Ship Research, 2023, 18(5): 234

    Download Citation

    EndNote(RIS)BibTexPlain Text
    Save article for my favorites
    Paper Information

    Category: Marine Machinery, Electrical Equipment and Automation

    Received: Jun. 29, 2022

    Accepted: --

    Published Online: Mar. 21, 2025

    The Author Email:

    DOI:10.19693/j.issn.1673-3185.02980

    Topics