OPTICS & OPTOELECTRONIC TECHNOLOGY, Volume. 21, Issue 3, 46(2023)

ResearchonElectricFieldMonitoringMethodof10kVT-Type CableJointUnderWetDefect

LIUGang, HUANGHua-feng, ZHANGYuan-ming, CHENChen, ZHUANGHai-lu, and GONGJin
Author Affiliations
  • [in Chinese]
  • show less

    In order to obtain an effective online monitoring method for T-shaped cable terminal joints deterioration, this paperfirstly simulates and analyzesthe electric field distributioncharacteristics ofT-typecablejointsunder typicalairgap moisture defects, and proposes a defect monitoring and identification method based on changes in electric field signals. Then the electric field signal monitoring test of the lower T-type cable terminal joint is carried out to verify the proposed method. Research results show that, for the deteriorated T-type cable terminal joint, when the humidity is sufficient, the effective value of the space electric field increases by 200%; and when the internal moisture causes partial discharge, the effectivevalueofthespaceelectricfieldincreasesby5~6times.Bycomparingtherisingrateoftheelectricfieldintensityin themonitoringlocation, itcanidentifywhethertheT-shapedcablejointhassignsofdeterioration.

    Tools

    Get Citation

    Copy Citation Text

    LIUGang, HUANGHua-feng, ZHANGYuan-ming, CHENChen, ZHUANGHai-lu, GONGJin. ResearchonElectricFieldMonitoringMethodof10kVT-Type CableJointUnderWetDefect[J]. OPTICS & OPTOELECTRONIC TECHNOLOGY, 2023, 21(3): 46

    Download Citation

    EndNote(RIS)BibTexPlain Text
    Save article for my favorites
    Paper Information

    Category:

    Received: Dec. 23, 2022

    Accepted: --

    Published Online: Dec. 28, 2023

    The Author Email:

    DOI:

    CSTR:32186.14.

    Topics