Acta Optica Sinica, Volume. 42, Issue 16, 1611002(2022)

Local Source-Translation CT Imaging for Testing In-Service High-Voltage Cables

Mingjuan Liao1,2, Lei Li2, Xiaojiao Duan1,2,3, Dabing Chen4, and Fenglin Liu1,2,3、*
Author Affiliations
  • 1Key Laboratory of Optoelectronic Technology & Systems, Ministry of Education, Chongqing University,Chongqing 400044, China
  • 2Industrial CT Non-Destructive Testing Engineering Research Center, Ministry of Education, Chongqing University, Chongqing 400044, China
  • 3Chongqing Zhence Science and Technology Co., Ltd., Chongqing 401332, China
  • 4Research Institute, State Grid Jiangsu Electric Power Co., Ltd., Nanjing 211103, Jiangsu , China
  • show less
    Figures & Tables(19)
    Geometric model of L-STCT system
    2D geometry model
    Data distribution in Radon space
    System area division
    Analysis of P points in each sub-area. (a) Area 1; (b) area 2; (c) area 3; (d) area 4
    Maximum projection coverage angle distribution in this system
    Maximum projection coverage angle distributions for light passing point M. (a) Horizontal line section view; (b) vertical line section view
    Simulation phantom
    Simulation results. (a) Reconstruction results for different source translation distances; (b) reconstruction results for different detector widths
    Magnified ROI images in Fig. 9(a)
    Reconstruction results obtained by changing distance from X-ray source to measured object
    Magnified ROI images in Fig. 11(a)
    Profiles along 50th row of image reconstructed with different system parameters. (a) Different source translation distances; (b) different detector widths; (c) different distances from X-ray source to measured object
    Experimental system of L-STCT
    Comparison of reconstruction results. (a) s=120 mm; (b) s=250 mm; (c) cable is not immersed in water; (d) cable is immersed in water for 10 h
    Comparison of immersion results. (a) Standing for 25 min; (b) standing for 4.5 h
    Illustrations of scanning modes. (a) STCT; (b) L-STCT
    • Table 1. Scanning parameters of simulation

      View table

      Table 1. Scanning parameters of simulation

      ParameterValue
      Distance from source to object h /mm120
      Distance from detector to object l /mm63
      Detector array number m1536
      Detector pixel size /mm0.085
      Source translation distance s / mm250
      Model radius R /mm50
      Distance from model center to coordinate origin a /mm35
      Number of samples per L-STCT n400
    • Table 2. Quantification indexes of reconstructed images with different system parameters

      View table

      Table 2. Quantification indexes of reconstructed images with different system parameters

      ParameterRMSESSIM
      Source translation distance s150 mm0.19090.7892
      200 mm0.18010.8219
      250 mm0.14520.8857
      Detector array number m15360.14530.8863
      25360.13360.9066
      35360.13020.9139
      Distance from source to object h70 mm0.13420.9067
      120 mm0.14530.8856
      170 mm0.17340.8348
    Tools

    Get Citation

    Copy Citation Text

    Mingjuan Liao, Lei Li, Xiaojiao Duan, Dabing Chen, Fenglin Liu. Local Source-Translation CT Imaging for Testing In-Service High-Voltage Cables[J]. Acta Optica Sinica, 2022, 42(16): 1611002

    Download Citation

    EndNote(RIS)BibTexPlain Text
    Save article for my favorites