Infrared Technology, Volume. 45, Issue 12, 1351(2023)
Reliability Image Recognition Method for High Temperature Operation of Power Stabilizer in Medium and Low Voltage Grids Based on Infrared Imaging
area was calculated to determine the reliability level. The results show that only two of the five test stabilizers are in an abnormal state; specifically, component 3 of stabilizer 2 is abnormal, and component 1 of stabilizer 5 is abnormal. The relative temperature difference of component 3 of stabilizer 2 was 82.32%, and the corresponding reliability level was level 2, with low reliability; the relative temperature difference of component 1 of stabilizer 5 was 91.35%, the corresponding reliability level was level 3, and the reliability was extremely low. Comparative experimental results show that the recognition accuracy of the proposed method reaches 92.3% or higher, which is superior to that of the comparison method and has a greater application value.
Get Citation
Copy Citation Text
DAI Zikuo, SHI Kejian, SONG Shida, LIU Yang, XU Yan. Reliability Image Recognition Method for High Temperature Operation of Power Stabilizer in Medium and Low Voltage Grids Based on Infrared Imaging[J]. Infrared Technology, 2023, 45(12): 1351
Category:
Received: Sep. 21, 2022
Accepted: --
Published Online: Jan. 17, 2024
The Author Email:
CSTR:32186.14.