Chinese Optics Letters, Volume. 7, Issue 6, 06539(2009)

Four-step DOAS calibration method of SO2 in flue gas

Tao Zhou, Bin Liu, and Changku Sun
Author Affiliations
  • State Key Laboratory of Precision Measurement Technology and Instruments, Tianjin University, Tianjin 300072, China
  • show less

    SO2 monitoring in the flue gas of a coal burning boiler is important for environmental protection. The nonlinearity of practical condition causes deviation from theoretical law. On the basis of the Lambert-Beer Law, a new four-step calibration method is introduced. This method includes cross section interpolation, weighting spectral region combination, acquiring the spectrum with new calibration devices, and least-square fitting. Compared with conventional methods, this new method is low cost, convenient, and accurate. In the proof test, SO2 samples with different concentrations are measured. The average errors are less than 1.5%, while the maximum deviation is less than 4.5%.

    Tools

    Get Citation

    Copy Citation Text

    Tao Zhou, Bin Liu, Changku Sun. Four-step DOAS calibration method of SO2 in flue gas[J]. Chinese Optics Letters, 2009, 7(6): 06539

    Download Citation

    EndNote(RIS)BibTexPlain Text
    Save article for my favorites
    Paper Information

    Received: Sep. 16, 2008

    Accepted: --

    Published Online: Jun. 8, 2009

    The Author Email:

    DOI:10.3788/COL20090706.0539

    Topics