Spectroscopy and Spectral Analysis, Volume. 33, Issue 9, 2407(2013)

Quantitative Analysis of Transformer Oil Dissolved Gases Using FTIR

ZHAO An-xin1,2、*, TANG Xiao-jun1, WANG Er-zhen1, ZHANG Zhong-hua1,3, and LIU Jun-hua1
Author Affiliations
  • 1[in Chinese]
  • 2[in Chinese]
  • 3[in Chinese]
  • show less

    For the defects of requiring carrier gas and regular calibration, and low safety using chromatography to on line monitor transformer dissolved gases, it was attempted to establish a dissolved gas analysis system based on Fourier transform infrared spectroscopy. Taking into account the small amount of characteristic gases, many components, detection limit and safety requirements and the difficulty of degasser to put an end to the presence of interference gas, the quantitative analysis model was established based on sparse partial least squares, piecewise section correction and feature variable extraction algorithm using improvement TR regularization. With the characteristic gas of CH4, C2H6, C3H6, and CO2, the results show that using FTIR meets DGA requirements with the spectrum wave number resolution of 1 cm-1 and optical path of 10 cm.

    Tools

    Get Citation

    Copy Citation Text

    ZHAO An-xin, TANG Xiao-jun, WANG Er-zhen, ZHANG Zhong-hua, LIU Jun-hua. Quantitative Analysis of Transformer Oil Dissolved Gases Using FTIR[J]. Spectroscopy and Spectral Analysis, 2013, 33(9): 2407

    Download Citation

    EndNote(RIS)BibTexPlain Text
    Save article for my favorites
    Paper Information

    Received: Jan. 27, 2013

    Accepted: --

    Published Online: Sep. 30, 2013

    The Author Email: An-xin ZHAO (zhaoanxin@126.com)

    DOI:10.3964/j.issn.1000-0593(2013)09-2407-04

    Topics